ANTEX A8 Fixed Capacitor Banks for
Power Factor Correction
wpeC.jpg (3738 bytes)
Applications : These Antex A8 series have been specifically designed for applications for power factor correction systems in conditions having heavy stress of non linear loads. The recommended areas for use are Paper Mills, Cement Plants, Data processing centers, printing presses, steel mills, induction furnaces and all users who are connected to AC/DC static continuity units. These result in reduction in demand charges, release of transformer capacity, reduction in transmission losses and improved system voltages. These capacitors are of robust design and are built for 7 years life. For more stringent applications, Saha Sprague offers the SPRAGUE™ fixed capacitors for power factor correction with a 20 years life.
Construction:
 
The Antex A8 series is designed using the Antex A7capacitors. These Capacitors are designed using two layers of Polypropylene films which have been vacuum deposited with a special combination of metal alloys to act as electrodes of the capacitor. This film is would into elements using tension which is computer controlled so as not to stretch the film at the same time to ensure there is no air trapped in between the layers. These elements are then impregnated in a special low viscosity fluid and then assembled into Aluminum Cans, built with special pressure interrupters. These precludes any possibility of explosion of the capacitor unit under extreme conditions.
 
These capacitor units are then connected in delta, house in a MS sheet housing , which is powder coated . Discharge resistors are then attached, and the units are then put into its various levels of conditioning and testing. Each System comes with an individual base data and is serialized for tractability.
 
These Units are designed for easy assembly and is completely modular right from the 5 KVAR units to the 25 KVAR units, and don’t require Banking heads or bases., A range of easy banking accessories are available on request.
wpe9.jpg (5691 bytes) Range of the Antex A8 PFC Capacitor
TECHNICAL SPECIFICATIONS:
Series
Antex B8.1
Antex B8.3
Antex B8.2
Rated Voltage
415/450
415/452
415/451
Design frequency
50Hz
50Hz
50Hz
Phase
three
three
three
Temp range
-25to +55 Celsius
-25to +55 Celsius
-25to +55 Celsius
Base DI-electric
BI-Axially oriented
BI-Axially oriented
BI-Axially oriented
 
Polypropylene Film
Polypropylene Film
Polypropylene Film
Electrodes
Special alloy
Special alloy
Special alloy
Electrode mode
Metalisation
Metalisation
Metalisation
Filler
Polyurethane
Polyurethane
Eco Friendly oil
Impregnant
YES
NO
YES
Losses
< 0.5W/KVAR
< 0.5W/KVAR
< 0.5W/KVAR
Pressure interrupter
yes
yes
yes
Compliance standards
IS 2834
IS 2836
IS 2835
Flame retardant construction
YES
YES
YES
Range
5,10,15,20&25
5,10,15,20&27
5,10,15,20&26
Bankable
yes
yes
yes
Failure warranty
2 years
2 years
3 years
Anti Explosion Warranty
5 years
5 years
5 years
Connection
delta
delta
delta
Discharge resistor
yes
yes
yes
Life design
50,000 hr.
30,000 hr.
50,000 hr.
Design base
UL,CSA,VDE, ISI,CPRI,ETNT
UL,CSA,VDE, ISI,CPRI,ETNT
UL,CSA,VDE, ISI,CPRI,ETNT

No. S-915, South Block,9th Floor, Manipal centre,47, Dickenson Rd, Bangalore – 560042Tel: 080 – 2509 2274,2509 2275

Email: contact@saha.net

 Top of Page